    摘要:

    为提高铁路接触网设备防雷水平,降低雷电绕击概率,本文在避雷线高度计算过程中额外考虑了保护角大小因素,利用被保护设备与避雷线位置的几何关系推导出了保护角大小与避雷线架设位置的数学关系,并建立了相应的数学模型。通过调整避雷线保护角大小,降低线路整体雷电绕击概率。参照准朔铁路接触网数据,对调整前后线路雷电绕击概率进行计算比较,发现调整后线路的雷电绕击概率降低20.65%,接近理论计算的最小雷电绕击概率,该方法能在不增加成本的条件下有效降低雷电绕击概率。

    Abstract:

    In order to improve the lightning protection level of railway catenary equipment and reduce the probability of lightning shielding failure, this paper considers the size of the protection angle in the calculation of the height of the lightning conductor, deduces the mathematical relationship between the size of the protection angle and the erection position of the lightning conductor by using the geometric relationship between the protected equipment and the lightning conductor, and establishes the corresponding mathematical model. By adjusting the protection angle of lightning conductor, the probability of lightning shielding failure is reduced. Referring to the OCS data of zhunshuo railway, the lightning shielding failure probability of lines before and after adjustment is calculated and compared. It is found that the lightning shielding failure probability of lines after adjustment is reduced by 20.65%, which is close to the minimum lightning shielding failure probability calculated theoretically. This method can effectively reduce the lightning shielding failure probability without increasing the cost.

    参考文献
    相似文献
    引证文献
引用本文
分享
文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:2021-08-19
  • 最后修改日期:2021-10-25
  • 录用日期:2021-10-27
  • 在线发布日期:
  • 出版日期:
Baidu
map
关闭